Pump Affinity Law Calculator
Calculate pump performance changes with speed or impeller diameter using affinity laws.
Introduction
Pump affinity laws predict how changing pump speed or impeller diameter affects flow rate (Q), head (H), and power (P). For variable speed drives (VSD), Q∝N, H∝N², P∝N³ — power reduction is cubic with speed.
How This Calculator Works
P₂ = P₁ × (N₂/N₁)³ for variable speed. p1 in kW is converted to W by engine; /1000 returns kW. Power is proportional to speed cubed.
Step-by-step process:
- Enter your input values in the calculator above
- The engine converts all inputs to SI base units (meters, kg, Pa)
- The formula is evaluated:
p1 * (n2/n1)^3 / 1000 - Result is formatted with the appropriate unit and precision
Calculation Example
Unit Conversion for Affinity Laws
**Speed units**
- 1 rpm = 1/60 rps
- 1 rps = 60 rpm
**Flow units**
- 1 m³/h = 0.2778 L/s = 4.403 US gpm
**Head units**
- 1 m = 3.28084 ft
**Power units**
- 1 kW = 1.341 hp
Affinity laws are ratio-based: Q₂/Q₁ = N₂/N₁, H₂/H₁ = (N₂/N₁)², P₂/P₁ = (N₂/N₁)³. Any consistent unit set works because only ratios are used.
Engineering Applications
- •VFD energy savings estimation
- •Pump speed selection
- •Impeller trimming
- •Retrofit evaluation